Table 1: Negative Wind Pressure Test Results
Configuration Test Ultimate Pressure (psf) Allowable Pressure (psf)
Active Ventilation Products 1 225 90
Aura Skylight Ventilator for the 2 223 89
Aura Whole House Ventilation System with Natural Light, #8x3/4" Panhead Screws, 6" O.C. (12 total) into 7/16" APA Rated OSB 3 227 91
Ultimate Pressure divided by a Factor of Safety of 2.5 in accordance with 24 CFR §3280.401(b).
Table 2: Aura Whole House Ventilation Design Recommendations for Manufactured Homes
Configuration
Performance
Aura Skylight Ventilator for the Aura Whole House Ventilation System with Natural Light #8 x 3/4" Screws at approx. 6-in. O.C. spacing (maximum) secured to 7/16" APA Rated OSB (minimum)
24 CFR §3280. 401 (b) Allowable Negative Pressure = -90 psf 24 CFR §3280.305(ii) Acceptable for use as a Wind Zone III exterior roof covering within 3'-0" from ridge and eave (overhang at sidewall) or sidewall if no eave is provided (-89 psf, design wind speed 110 MPH) AAMA 1600-90, Section 8.3.1
Interior (Negative) Pressure
Exterior Performance Class: 100

Design Pressure = 100 psf
Results correspond to interior (negative) pressure test only. Both exterior (positive) and interior (negative) pressure test results are required to establish an actual Exterior Loading Performance .Classification in accordance with AAMA 1 600-9O, Section 8.3.1. Exterior (positive) pressure testing may result in an Exterior Performance Classification lower than the value noted herein.
APPENDIX A:

TEST DATA

Test Configuration:
Date: 10/17/01

Test Performed: 24 CFR §3280.401 (b)
Performed By: Shawn Weldy
Witnessed By: John Kirkwood Reviewed By: David R. Tompos, P.E.

Specimen: Aura Skylight Ventilator for the Aura Whole House Ventilation System with Natural Light
Fastening: #8 x 3/4" screws at 6" o/c (12) total
Sheathing: 7/16" APA Rated OSB
Design Load (W): 89 psf in accordance with 24 CFR §3280.305(c)(ii)

Specimen 1
Load Increment Manometer Reading (in.) Pressure (psf) Total at Glazing (in.) Sheathing at Fastener Line (in.) Net at Glazing (in.)
-- 0.0 0 0.000 0.000 0.000
0.25W 4.3 23 0.038 0.003 0.035
0.50W 8.6 25 0.083 0.004 0.079
0.75W 12.8 68 0.144 0.006 0.138
1.00W 17.1 89 0.218 0.010 0.208
1.25W 21.4 110 0.283 0.011 0.272
Ultimate 42.8 225 -- -- --
Pressure computed with an assumed unit weigh of water equal to 62.4 lb/ft3 or 5.2 psf/i n.
Mode of Failure: No failure noted at maximum test pressure.
Specimen 2
Load Increment Manometer Reading (in.) Pressure (psf) Total at Glazing (in.) Sheathing at Fastener Line (in.) Net at Glazing (in.)
-- 0.0 0 0.000 0.000 0.000
0.25W 4.3 22 0.049 0.000 0.049
0.50W 8.6 45 0.148 0.001 0.147
0.75W 12.8 67 0.151 0.003 0.148
1.00W 17.1 89 0.206 0.003 0.203
1.25W 21.4 111 0.261 0.003 0.258
Ultimate 42.8 223 -- -- --
Pressure computed with an assumed unit weigh of water equal to 62.4 lb/ft3 or 5.2 psf/i n.
Mode of Failure: No failure noted at maximum test pressure.
Specimen 3
Load Increment Manometer Reading (in.) Pressure (psf) Total at Glazing (in.) Sheathing at Fastener Line (in.) Net at Glazing (in.)
-- 0.0 0.0 0.000 0.000 0.000
0.25W 4.4 23 0.030 0.002 0.028
0.50W 8.6 45 0.071 0.005 0.066
0.75W 13.0 68 0.120 0.007 0.113
1.00W 17.2 89 0.160 0.010 0.150
1.25W 21.6 112 0.204 0.012 0.192
Ultimate 43.6 227 -- -- --
Pressure computed with an assumed unit weigh of water equal to 62.4 lb/ft3 or 5.2 psf/i n.
Mode of Failure: No failure noted at maximum test pressure.
APPENDIX B:

MANUFACTURER'S INSTALLATION INSTRUCTIONS
AURA WHOLE HOUSE VENTILATION SYSTEM WITH NATURAL LIGHT

The following items need to be performed for the proper installation of the Aura Whole House Ventilation System with Natural Light. It is not necessary or required that the order be followed as printed. You can decide what it the best sequence for your particular plant.

1. Foam the lower ring and flex-duct assembly to the attic side of the ceiling.

2. Reach inside the flex-duct and cut the ceiling board out using the lower ring as a guide.

3. Cut a hole approx. 10-1/2" in diameter in the decking directly above the previously installed lower ring and flex-duet assembly.

4. Reach down and obtain the upper end of the flex-duct and insert it in the upper ring. The raised part of the upper ring should be upward.

5. Pull the flex-duct taught and cut off the excess duct. The flex-duct will hold onto the upper ring without fastening.

6. Foam the upper ring to the decking making sure no inside air can get into the attic.

7. Install the Aura Vent with clear lid over the upper ring and flex-duct assembly in the following manner.

A. Apply sealant to under side of the flange.

B. Place over the upper ring and flex-duct assembly.

C. Fasten to the decking using 12 #8 x 3/4" screws 6" on center.

8. Install the adjustable ceiling vent by inserting into the lower ring and flex-duct assembly.

9. Screw the ceiling vent ring through the ceiling into the lower ring using the holes provided in the ceiling vent ring.

10. To adjust the ceiling vent insert fingertips into the ridge at the lower end of the ceiling vent and pull down for more ventilation or push up for less.

Figures
niafigure1
niafigure2
niafigure3
Figure 2: Typical Skylight Test Set-up
niapic